Infrared Inspecting New Equipment

WHY BRAND NEW INSTALLATIONS NEED TO BE THERMALLY INSPECTED

    • New Installation Thermo PDF
    • Thermography Inspection Performed on December 14th 2011
    • The Image is of a “Factory Installed” Bus Connection from the 3,000 amp vertical bus to the primary side of an 800 amp distribution circuit breaker.
BusConnection BlueField 225x300 Infrared Inspecting New Equipment
    • This temperature abnormality was found during the Thermography inspection on phase c of the newly installed GE switchgear. The temperature difference between phase C and phase B is 20 degrees ferenheight (Image #2). The breaker was aproximatley 30% loaded at the time of inspection (phase C-278amps phase B- 284amps). After removing the factory installed GE circuit breaker we found that the insulation tape had overlapped and restricted the current flow from the main bussway in the gear to the circuit breaker lug (Image #1).
BusConnection Abnormal 300x224 Infrared Inspecting New Equipment
    • The repair was made and the tape was properly removed from the switch gear (Image #3). A re-scan was perfomed on the circuit breaker (Image #4) and phase c was actually running 2 degrees cooler than phase b.
BusConnection Fixed 224x300 Infrared Inspecting New Equipment BusConnection Normal 300x225 Infrared Inspecting New Equipment

ico tag Infrared Inspecting New Equipment Tags:  

Del.icio.us
delicious Infrared Inspecting New Equipment
Facebook
facebook icon Infrared Inspecting New Equipment
TweetThis
tweet Infrared Inspecting New Equipment
Digg
digg Infrared Inspecting New Equipment
StumbleUpon
stumble Infrared Inspecting New Equipment


Copyright © Cooper Electric [Infrared Inspecting New Equipment], All Right Reserved. 2013.

Source: http://cooper-electric.net/infrared-inspecting-new-equipment/

electrician work electrical training electrician apprenticeship

No comments:

Post a Comment